欢迎访问格林思科实业有限公司官方网站

Online UPS (208V/3Ph ) with 0.9 or 1.0 Output Power Factor

工频UPS

产品详情

Applications

IDC room, Large and medium computer networks, Banks, Securities, Communication centers, Semiconductor production lines, Large-scale automated production and control systems, Large gymnasium, Conference rooms, Theaters, Highways, Railways, Tunnels and lighting systems.

Introduction

Online UPS provides maximum protection for vital mission-critical networks, security applications (electro-medical) and industrial applications thanks to its outstanding mechanical and electrical design.The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.
The UPS uses on-line double conversion technology (VFI) with and isolation transformer on the inverter output.UPS is supplied with Watch & Save 3000 software as standard and can be remotely monitored using the Power NetGuard system from anywhere in the world. Additional battery extension packs allow the standard battery runtime to be extended up to several hours

Features

●Minimum impact on supplies easy sourse
Input current distortion <4% for the UPS with filter with sinusoidal absorption to remove the risk of
resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance. This enable UPS to deliver maximum performance levels regardless of the installation environment. With these input features UPS can achieve significant savings in terms of sizing and power supply sources-isolation transformers and generators over less sophisticated power systems.
●Maxmum battery care 
Battery deep discharge protection; Temperature compensating charger; Built-in automatic and manual battery test feature
●Simple to install
Capability to install the UPS into any distribution system (neutral not required on rectifier input);Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation (Necessary on UPS without an output transformer).
●High reliability 
Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting,drives and industrial processes) and an isolation transformer on the inverter output;
●Full microprocessor control with no-break static and manual bypasses;
●IGBT technology.
●High level diagnostics: event lo with 128 messages, states,measurements and alarms available from the built-in LCD in several languages;
●BACK FEED protection: to avoid energy feeding back into the mains supply should a fault occur.
●Connect up to 8 units in parallel or N+1 redundancy, even of different power ratings.The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOOSED LOOP).
●Low consumption levels
UPS can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity should the mains fail.
●Advance communication 
● Compatible with TeleNetGuard for remote maintenance;
● Advanced, multi-platform communication for all operation systems and network environments: Watch & Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 2008, ista,2003, XP; Mac OS X,Linux, Novell and most popular Unix operating systems
● The UPS is supplied with a cable for direct connection to the PC(Plug and Play);
● RS232 or RS485 double Serial port;
● Installation slot for an Emergency Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency;
● Generator interface: enables desynchronisation of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge

Specification  

Model

GS8331C 10KVA-200KVA (208/220VAC/3Ph)

Capacity

10KVA

20KVA

30KVA

40KVA

60KVA

80KVA

100KVA120KVA160KVA

200KVA

10KW20KW30KW40KW60KW80KW100KW120KW160KW200KW
Input
Voltage208VAC/220VAC;3-phase+4wires
Voltage range±25%
Frequency50/60HZ
Frequency range±5%
THDi<3%
Power factor>0.9
Bypass voltage208VAC/220VAC;3-phase+4wires
Input frequency50/60HZ±10%
Output
Voltage208VAC/220VAC;3-phase+4wires
Voltage stability±1% stead status
Frequency50/60Hz±0.05Hz
Power factor0.9 or 1.0
Overload≤110%for 60 minutes;≤125% for 10min;≤150% for 1min
Current Crest Ratio3:1
Transfer time0 ms
Battery
DC voltage384VDC/432VDC/480VDC,VRLA,gel,NiCd battery
Charge time8 hours to 90% (it means standard model which battery inside UPS)
DC ripple voltage<1%
LCD displayUPS status, input/output voltage and frequency,battery voltage, capacity,load temperature,history records,adjust Voltage,ECO mode
CommunicationRS232, AS400,RS485,SNMP (Optional),USB(Optional)
Efficiency>98%
ProtectionIP21
Working temperature0~40°C
Humidity0~95% non-condensing
Storage temperature-25°C~70°C
Elevation1000M
Noise<45dB
Dimension(mm)550x720x1200800x740x14001050x740x1400
Weight(kgs)

190

210

290

340

440

520

770

855