欢迎访问格林思科实业有限公司官方网站

电力 inverter 220VAC/48VDC

Widely used in power plants,substations,hydropower stations,communication,data centers,signals,railways,industrial production,military research and other fields.

产品详情

Application:
Widely used in power plants,substations,hydropower stations,communication,data centers,signals,railways,industrial production,military research and other fields.
Introduction:
Our industrial inverter is the fourth generation of intelligent inverter power supply which is developed with new digital technology to meet the high reliability requirement of power system. Using SPWM pulse width modulation technology,IGBT power module and output isolation transformer.The output of inverter power supply is a pure sine waveform with features of stable frequency and stable voltage, filtering noise, free from grid fluctuation and low distortion. The inverter has the advantages of strong load-carrying capacity, good load compatibility, wide DC input voltage range, etc.
Our industrial inverter has 3 modes which can be choosed (optional ): Pure DC power supply mode: pure DC input, when DC power cut off,the inverter is shutdown to stop working. DC main supply mode: DC and AC double inputs, DC supply power in priority, AC standby; when DC power cut off,inverter automatically switches to AC power supply. AC main supply mode: DC and AC double inputs, AC power supply is priority, DC standby; when AC power cut off, inverter automatically switches to DC power supply.
Features:
Adopted SPWM pulse width modulation technology, with IGBT power module and output isolation transformer.
Design of user-friendly LED /LCD interface.
Automatic bypass conversion, to achieve uninterrupted work load.
With RS232 communication interface. (optional)
With anti-back connection, under-voltage, over-voltage, overload, short circuit protection,ect.
Specification:

Model

TG3117A-1KVA

TG3117A-2KVA

TG3117A-3KVA

TG3117A-5KVA

Rated capacity

1000VA

2000VA

3000VA

5000VA

Rated output power

800W

1600W

2400W

4000W

DC input

Rated input voltage

48Vdc

Rated input current

21A

42A

63A

105A

Cutoff voltage range

42V60Vdc

Turn on voltage range

44V60Vdc

AC input

Bypass voltage

220Vac±15%

Rated input current

4.5A

9.1A

13.6A

22.7A

Transfer time

≤5ms

AC output

Output voltage

220Vac50Hz

Waveform

Pure sine waveform

Output current

3.6A

7.2A

10.8A

18A

Output voltage accuracy

220Vac±2%

Output frequency accuracy

50Hz or 60Hz

THD

≤3%(Linear load)

Dynamic response time

Load current changes from 25%50%75%output voltage changes≤10%recovery time20ms

Power factor

0.8

0.8

0.8

0.8

Overload

When load current is 120%auto conversion to bypassautomatic recovery after the overload disappears

Efficiency

≥85%80% Resistive load

Work environment

Insulation strength

1500Vacfor 1 minute

Noise(1M)

≤60dB

Environment temperature

-10℃~45

Humidity

2090%Non-condensing

Altitude

≤2000m

Cooling

Forced fan

Indicator

LCD display

Input and output voltage, frequency, battery voltage, load percentage, temperature, working state

LED indicator

ACworkoverloadbatteryfault

Mechanical

Rack mount(mm)

19”rack mount

/

Tower(WxDxH)

/

tower

Weight

3kgs

5kgs

7kgs

 12kgs

Color

Black/gray