三相模块化变频电源
模块化变频电源
Introduction:
Our
company's modular frequency converter adopts an active PFC thyristor
rectifier+high-frequency isolated bidirectional DC/DC
converter+high-frequency three-phase or single-phase sine inverter
circuit topology, omitting the output power frequency isolation
transformer that has the greatest impact on the volume and weight of the
variable frequency converter. Under the same output power capacity, our
modular frequency converter is one-third of the current volume and
one-quarter of the weight of tower frequency converters.
Our modular
frequency converter adopts standard 19 inch 2U modular chassis
structure. Each power module has the same structure, and can achieve
rated power output capacity of 5KW to 15KW single-phase to 150KW
three-phase four wire for frequency converters according to different
applications.
For single-phase frequency converters, a silicon
carbide high-frequency power factor correction boost rectifier circuit
is used; For three-phase frequency converters, a silicon carbide full
bridge PWM rectifier circuit is adopted; The purpose of achieving high
input power factor and low input current harmonics in variable frequency
converter power supplies.
The input power supply is rectified by an
active PFC and outputs a DC bus voltage. The DC bus voltage is connected
to a SIC high-frequency isolated bidirectional DC/DC inverter, and the
input circuit and output circuit are electrically isolated through a
high-frequency isolation transformer. And the high-frequency isolated
DC/DC circuit is a bidirectional energy conversion circuit, which can
achieve bidirectional automatic transmission of energy from input to
output or from output to input. The other circuit is connected to the
auxiliary power supply DC/DC isolation converter, providing various
voltage auxiliary power supplies for the entire module. Multiple
high-capacity supporting capacitors are connected in parallel to the DC
bus,which not only achieves the filtering function of the DC bus, but
also provides sufficient instantaneous power capacity for impulse loads.
This
series of modular frequency converters not only adopt the latest
high-frequency inverter circuit topology design and control algorithms,
but also adopts multiple proprietary control technologies and
manufacturing processes of our company that has continuously developed
and optimized in the variable frequency converter industry for more than
20 years. These proprietary technologies include but are not limited to
the following: "silicon carbide tube parallel drive and protection
technology", "single-phase active PFC rectification technology",
"three-phase PWM rectification technology", "SVPWM wave generation
control technology", "instantaneous voltage waveform control
technology", "wave by wave current limiting control technology",
"unmanned adaptive synchronous parallel operation control technology",
"power module hot swap technology" and other proprietary technologies
and rigorous design and manufacturing processes of our company, Ensure
that the quality performance of this series of modular frequency
converter equipment reaches the highest level in the field in China.
Advantages:
Active PFC thyristor rectifier. The input harmonic current is small THDi ≤ 3%, the input power factor is high PF ≥ 0.99.
Using
silicon carbide power switching devices to form a full bridge inverter
or DC/DC converter. The switching frequency is high from 40KHz to 80KHz,
with fast control speed and high accuracy. The output AC ripple is
small, and the sine wave shape is extremely smooth.
Using high frequency isolation transformer inside, with small size and weight.
Due
to the high switching frequency of inverter, with small size and
weight, low heat generation of the inverter, the inverter achieves
silent operation of the variable frequency converter power supply.
With standard modular design. Implement modular hot swapping function.
Each
power module can have power capacity of up to 15KVA, and multiple power
modules can be connected in parallel for expansion or redundant power
supply based on the output power capacity of the variable frequency
converters.
Specification:
Description | Specification | |
Model | MFC series Modular Frequency Converters | |
System Capacity(KVA) | MFC5011-15KVA(Single phase); MFC5033-30KVA to 150KVA(three phases) | |
Environment | Work environment | Indoor type or IP65 outdoor type |
Humidity | ≤95%,No condensation | |
Work temperature | -20℃~+45℃ | |
Storage temperature | - 40℃~65℃ | |
Altitude | 79kPa ~106kPa,<2000m | |
Cooling | Cooling fan | |
Input | Rated voltage | Single phase 110V/220V/260VAC; Three phases 200V/380V/415V/440V/460VAC |
Voltage range | ±20% | |
Power mode | Single phase+PE ground; three phases/3Wires+PE ground or 3 phases/4 Wires+PE ground | |
Rated frequency | 50Hz,60Hz,400Hz | |
Frequency range | ±10Hz | |
Power factor | ≥0.99(Remark: >30% rated current) | |
THDi | THDi≦3%(Remark:>50% rated current) | |
Hot swap and instant surge current | <120% rated current | |
Output | Output power mode | Single phase or three phases/3 wires |
Output rated voltage | Single phase 110V/220V/260VAC; Three phases 200V/380V/415V/440V/460VAC | |
Output voltage regulation range | 50V~+20% rated output voltage | |
THDu | THDu≦0.5% | |
Output voltage peak | CF=1.4±0.1(Remark: no load) | |
coefficient | ||
Static≦0.5v,Dynamic≦±1% Rated voltage(Remark:0~100%ladder type load) | ||
Voltage stabilization rate | ||
When the rated load suddenly increases/decreases at 100%, the instantaneous change rate of output voltage (Sags and Swells) is ≤ ± 3%, and it returns to the rated output voltage within 0.5 fundamental cycles (8ms). | ||
Output rated frequency | 50Hz,60Hz,400Hz | |
Output frequency accuracy | 0.001Hz | |
Output frequency stability | ≦0.01% rated output frequency(Remark:0~100% output frequency is stable when load changes) | |
Rated output current | 20A | |
Overload ability | 125% rated current>10 min,150% rated current >30s | |
Capable of withstanding an instantaneous peak current impulse of 3 times the rated output current. When the instantaneous peak current exceeds 3 times the rated output current, the inverter power supply will trip in reverse time. (Inverse time trip, meaning that the larger the current, the shorter the trip protection time) | ||
Unbalanced three-phase output voltage | ≦±1% rated voltage | |
Phase angle of three-phase output voltage | 120 ° (±0.1 ° ) | |
Efficiency | ≥95%(Remark:100% rated current) | |
Structural performance | Main circuit topology | High frequency boost rectifier circuit, high frequency three-phase PWM rectifier circuit, high frequency three-phase full bridge inverter circuit |
Modulation | SVPWM Space vector pulse width modulation method | |
Voltage control mode | Instantaneous voltage waveform feedback control method | |
Switch frequency | ≥40KHz~80KHz | |
Main control processor chip | Domestic DSP processor, main frequency 150MHz, single core or imported TMS320F28337, main frequency 200MHz, dual core | |
Display | 3.12-inch monochrome LCD display screen+touch operation buttons | |
Display | Display | When the input power supply experiences phase sequence, phase loss (three-phase imbalance), undervoltage, overvoltage, overcurrent, short circuit, or DC bus overvoltage, the power module will shut down for protection and display fault information. (Protection threshold can be set arbitrarily) |
Display | When there is a phase loss, undervoltage, overvoltage, overcurrent, or short circuit in the output power supply, the power module will shut down for protection, disconnect the output, and display fault information (the protection threshold can be set arbitrarily) | |
Protection | Heat radiator temperature too high (cooling fan failure), power module synchronization failure shutdown protection and disconnection of output and display of fault information (temperature protection threshold can be set arbitrarily) | |
Output current limiting function | Instantaneous peak output current limiting, with arbitrary setting of limiting threshold (wave by wave limiting control technology) | |
Input display | Display the three-phase line (phase) voltage, frequency, three-phase line current, apparent power, active power, reactive power, and power factor of the input power supply. (Display and measurement accuracy is 0.5 level, with 1 decimal displayed) | |
Output display | Display the three-phase line (phase) voltage, frequency, three-phase line current, apparent power, active power, reactive power, and power factor of the output power supply. (Display and measurement accuracy is 0.5 level, with 1 decimal displayed) | |
Parameter display | System operating time, DC bus voltage, switching frequency setting value, output voltage setting value, output frequency setting value, and radiator temperature. | |
Faulty display | Display fault alarm information in the form of text scrolling lights | |
Operation display | Display operation prompt information and troubleshooting methods in the form of text scrolling lights | |
Others | Voltage resistance and insulation strength | There should be no breakdown or ignition phenomenon (leakage current<10mA) between the input/output port and the chassis at 2500V/AC for 1 minute |
Insulation resistance | Input/output port to shell>100M Ω (test voltage 500Vdc) | |
Noise | ≤55dB | |
Module Dimension | 19”/2U height(W 48.26cm x H 4.445cm x D 58cm) | |
Module weight | 11KGS | |
Design life | 20 years |