Modular UPS 330KVA-1500KVA;output PF:1.0
Modular UPS is adpoted latest IGBT three-level and DSP controlling technology,with hot-swappable,online and double conversion and N+1 parallel redudancy functions for sensitive equipments.
Application
IT Servers, Data-Centers, Critical network devices, Sensitive electronic, Telecom, Hospitals, Banks, Offices, and other business,ect.
Introduction
MPS series is a high frequency modular online UPS system. The system are composed of three modules: Display & Control module, Inverter module and Bypass module.
The inverter module is designed for hot-swappable. Modular design ensures flexible options for expansion. Redundant UPS technology allow users to scale their power capacity and provide continuous and highest availability. Great power density ensures a small footprint and low heat dissipation. Rich management and communication functions ensure a friendly man-machine conversation interface.
Features
● Large capacity: maximum capacity of unit UPS is up to 1500KVA/1350KW
● Superior energy saving:Efficiency>96% at 50%-75% rated load and >95% at 25% rated load;Input PF=1,input THDi<3%
● Easy to install: top or bottom cabling, no need of input cabling cabinet
● Easy to maintain:full front access, UPS failed part can be replaced shortly
● Easy to modify:The numner of battery cells can be configured flexibly, the original batteries can be used when modifying the legacy system,the batteries can be replaced in time when it fails without interrupting the normal operation of UPS
● Extra large LCD or touch screen display English, Russia, French,Spanish and so on
● Advanced distributed active parallel technology realize operation of 4 ups and online capacity expansion
● Adoptive to severe power grid environment due to extra wide input voltage and frequency ranges
● Intelligent battery management maintains battery automatically to prolong battery life
● UPS power modules support hot swappable,capacity upgraded extremely simple.
● Super ability for overload and shortcircuit, ensure the system stability and safety under the limit state of system
Specification
Model | MPS9330C 330KVA-1500KVA | ||||||||
Capacity | 330KVA | 400KVA | 500KVA | 600KVA | 800KVA | 1000KVA | 1200KVA | 1400KVA | 1500KVA |
330KW | 400KW | 500KW | 600KW | 800KW | 1000KW | 1200KW | 1400KW | 1500KW | |
Input | |||||||||
Voltage | 380/400/415VAC;3-phase+4wires | ||||||||
Voltage range | 208-478VAC | ||||||||
Frequency | 50/60HZ | ||||||||
THDi | <3% | ||||||||
Power factor | >0.99 | ||||||||
Soft start | 5-30s can be settable | ||||||||
Bypass voltage | 380/400/415VAC;3-phase+4wires | ||||||||
Input frequency | 40-70HZ | ||||||||
Output | |||||||||
Voltage | 380/400/415VAC;3-phase+4wires | ||||||||
Voltage stability | ±1% stead status | ||||||||
Frequency | 50/60Hz±0.05Hz | ||||||||
Power factor | 1.0 | ||||||||
Overload | ≤110%for 60 minutes;≤125% for 10min;≤150% for 1min | ||||||||
Current Crest Ratio | 3:1 | ||||||||
Transfer time | 0 ms | ||||||||
Battery | |||||||||
DC voltage | 384VDC/432VDC/480VDC,VRLA,gel battery | ||||||||
Charge time | 8 hours to 90% (it means standard model which battery inside UPS) | ||||||||
DC ripple voltage | <1% | ||||||||
LCD display | UPS status, input/output voltage and frequency,battery voltage, capacity,load temperature,history records,adjust Voltage,ECO mode | ||||||||
Communication | RS232, AS400,RS485,SNMP (Optional),USB(Optional) | ||||||||
Efficiency | >96% | ||||||||
Protection | IP21 | ||||||||
Working temperature | 0~40°C | ||||||||
Humidity | 0~95% non-condensing | ||||||||
Storage temperature | -25°C~70°C | ||||||||
Elevation | 1000M | ||||||||
Noise | <65dB | ||||||||
Power module | PM10:10KVA/9KW:20KGS,PM20:20KVA/18KW:30KGS,PM30:30KVA/27KW:35KGS,PM40:40KVA/36KW:40KGS | ||||||||
PM50:50KVA/45KW:48KGS | |||||||||
Dimension(mm) | Power module:440x650x132 | ||||||||
600x850x1350 | 600x1050x1900 | 1800x850x1900 | 2950x850x1900 | 4780x1050x1900 |