Frequency converter(10KV/11KV/13.8KV) 400KVA-3000KVA
HFC high-power indoor variable frequency converter power supply equipment is our standard products. This series of products is specially used in the indoor or cabin environments such as Navy,port,dockyard,shipyard,shiprepair,shipbuilding,factories, ships, and marine drilling platforms which need high-power variable frequency converter power supply with high reliability,which is made by the world-class technology of ours.
Introduction:
HFC high-power indoor variable frequency converter power supply equipment is our standard products. This series of products is specially used in the indoor or cabin environments such as port terminals, repairing shipyards, floating docks, ships, and marine drilling platforms which need high-power variable frequency converter power supply with high reliability.
This series of products adopts the design of large and forced air cooling system, and the equipment cabinet is equipped with a detachable ABS resin dust-proof ventilation filter. The equipment protection level reaches IP32, which meets the design standards and specifications of marine equipment. This series of products adopts standard module structure design, which can flexibly carry out different equipment layout designs and a variety of single power supply power capacity designs according to customer requirements. The single power supply power capacity can reach 12 MVA. The series product adopts the following proprietary technologies and characteristics:
1.2 Adopting the special large force air cooling technology and dust protection technology of the cabinet, the protection level of the cabinet body reaches IP32 under the premise of ensuring sufficient heat dissipation in the cabinet. This ensures that the equipment is protected from the influence of dust and moisture in the worse operating environment and can operate safely and reliably at 100% full load for a long time.
1.4 The latest instantaneous voltage waveform control technology is adopted. Output voltage fluctuation ≤ 0.5 V; The effective value of the output voltage changes instantaneously(voltage temporary drop) when the load is suddenly added / subtracted, ≤ 3% and returns to the rated output voltage value within 0.5 fundamental wave cycles.
The three-stage sinusoidal filtering technology of inverter output is adopted. The output impedance of sinusoidal filter is greatly reduced and the output power supply quality is improved.
1.6 The master-slave synchronization parallel technology is adopted. Realize the parallel operation of any multiple variable frequency converters power supply equipments without circulation.
The power switch device uses the fourth-generation SKIIP IPM high-power intelligent power module produced by Semikron in Germany; The main control chip uses DSP, the latest generation of TMS320 F28335-32-bit with floating-point motor control special digital signal processing functions; The driving transmission mode adopts 5MHZ fiber optic drive transmission; The inverter modulation method uses the latest SVPWM space vector pulse width modulation method.
Filter hoisting unit or 12 pulse rectifier Transformer: Using our own filter hoisting technology, filter the input harmonic current of shore variable frequency converter to reduce the harmonic interference to the input grid.
6 pulse or 12 pulse rectifier module components: Adopt diode rectifier module or Silicon controllable rectifier module + heat pipe radiator + German EBM shaft flow cooling fan.
Inverse unit: Adopt the fourth-generation SKIIP IPM intelligent power module from Germany+ Japan Nippon Chemi-con large-capacity electrolytic capacitor + flexible laminated mother row + large centrifugal air cooling fan. The drive and alarm signal of inverse unit are connected to the main control board through optical fiber, and the running information of the inverse unit is connected to the main control board through CAN bus, which greatly improves the control performance of the inverse unit, the display of operation information and the judgment and location of fault information.
Cross-flow side blowing cooling fan: Adopt the long-life cross-flow side hairdryer in China. The fan is installed in the cabinet door with IP32 detachable cleaning ABS resin ventilation filter mesh to inhale the indoor air outside the cabinet, and through the top of the cabinet with large air centrifugal fan emits outside the cabinet, The air circulation of the large amount of air required to be heat dissipation in the cabinet.
Technical Specification:
No. | Specification | 400KVA | 630KVA | 800KVA | 1000KVA | 1250KVA | 1600KVA | 2000KVA | 3000KVA |
Input | Voltage | 380VAC±10%, 10KV±10%,Voltage can be customized per customersneeds | |||||||
Rated frequency | 50/60Hz±10% | ||||||||
Phase | 3 phases/3 wires or 3 phases/5 wires | ||||||||
Rectifier | 6pulse rectifier or 12 pulse rectifier | ||||||||
Power factor | >0.95 | ||||||||
THDi | <35% at 6pulse of 100% load, <15% at 12 pulse of 100% load | ||||||||
Output | Voltage | 440VAC(output voltage can be continuously adjustable according to customersneeds | |||||||
Current | 525A | 826A | 1050A | 1312A | 1640A | 2100A | 2624A | 3937A | |
Capacity | 400KVA | 630KVA | 800KVA | 1000KVA | 1250A | 1600KVA | 2000KVA | 3000KVA | |
Phase | 3phases/3 wires | ||||||||
Voltage stabilzing rate | static:<0.5V;dynamic<±1%(0-100% load);when 100% load is added or reduced, voltage changes<3%,recover to rated output voltage within 0.5 base wave cycle | ||||||||
Frequency | 50/60Hz(precision:0.01) | ||||||||
Frequency stabilzation | <0.01% ( when load changes at 0-100%) | ||||||||
Overload ability | when 150% output,warning,cut off output, display faults;Can withstand 3 times instantaneous current impact, when the impact current is greater than 3 times, the trip protection | ||||||||
THDu | <1%( no load or linear load) | ||||||||
Voltage Peak coefficient | 1.4±0.1(no load) | ||||||||
Vlotage unbalance of 3 phases | <1% | ||||||||
Voltage phase angle of 3 phases | 120°(±0.1°) | ||||||||
Efficiency | >95%(at 100% load) | ||||||||
Performance | Main power topology | Main power topology of frequency converter is adopted SKIIP fourth generation half-bridge intelligent power module from SEMIKRON in Germany to be composed of 3 pcs of all-bridge inverter circuits | |||||||
Inverter modulation method | SVPWM(Space vector pulse width modulation method) | ||||||||
Control method of voltage-stabilzation | Instantaneous voltage waveform feedback control method | ||||||||
Switch frequency of inverter | 3.6KHZ-6KHZ(can be customized according to customersneeds) | ||||||||
PWM drive transmission Mode | 5MHZ fiber optical driver transmission | ||||||||
Master processor | TMS320F28335,main frequency:150MHZ | ||||||||
Touch screen | 10.4",resolution ratio:1024*600(HD) | ||||||||
Analog signal input port | 22 Differential ports,precision 12,transfer time:80ns | ||||||||
Digital input port | 8 dry contacts | ||||||||
Digital output port | 6 dry contacts,250VAC/3A | ||||||||
Communication | RS485(insulation voltage:2500Vrms,transimmison speed:500K/20Mbps,256 bus nodes;CAN port:insulation voltage:2500VDC,transimmision speed:1MHZ,110 nodes,can be paralled with many frequency converters working together | ||||||||
Protection | Trip protection | Input phase sequence, phase deficiency, undervoltage, overvoltage, overcurrent, short circuit, DC bus overvoltage, trip protection(protection value can be set arbitrarily) | |||||||
Output phase sequence, phase deficiency, undervoltage, overvoltage, overcurrent, short circuit, DC bus overvoltage,Output voltage harmonic overvalue, trip protection(protection value can be set arbitrarily) | |||||||||
The temperature of input transformer,output transformer,sine filter, rectifier,IPM power modules is higher than normal temperature(temperature value can be setted arbitrarily) | |||||||||
Warning protection | The temperature of input transformer,output transformer,sine filter, rectifier,IPM power modules reaches the value of fan working, fan starts working(temperature value can be setted arbitrarily) | ||||||||
Considering the control of different power loads, when the output load capacity reaches any set value, an acoustic light alarm signal is issued. When a load alarm signal is issued, the overload is still more than 1 minute above the set value, and the trip protection(protection value can be arbitrarily set). | |||||||||
Display | Input display | Input Voltage Three-phase Line(Phase) Voltage, Frequency, Three-Phase Line Current, Input Voltage Harmonic Analysis, Visible Power, Active Power, Reactive Power, Power Factors, Active Power Measurement, Reactive Power Measurement(Display and Measurement Accuracy is 0.5 | |||||||
Output display | Input Voltage Three-phase Line(Phase) Voltage, Frequency, Three-Phase Line Current, Input Voltage Harmonic Analysis, Visible Power, Active Power, Reactive Power, Power Factors, Active Power Measurement, Reactive Power Measurement(Display and Measurement Accuracy is 0.5 | ||||||||
System Run Parameters Display | System operating time, DC bus voltage, power module output current, inverter switching frequency, output voltage setting value, output frequency setting value, input transformer temperature, rectifier temperature, three-phase power module temperature, sinusoidal filter temperature, output transformer temperature | ||||||||
Fault information display | Graphical display of input and output power fault alert information, pre-charge fault information, power module fault information, component overtemperature fault information, permanent record of all operating parameters for fault analysis | ||||||||
Operation display | Display system status, operation tips, fault handling and handling methods in the form of led banner to facilitate users operation and maintenance of equipment | ||||||||
Drawings Data Display | Each variable frequency converter has permanent preservation of drawings, instructions and other data, very convenient on the display screen to display, consult | ||||||||
Communication | RS485 communication | Can upload all system operation data, fault information and remote control of variable frequency converter equipment by the host computer, communication protocol, standard: modbus, transmission medium, twisted-shielded cable | |||||||
CAN bus port | Can realize multiple frequency converters working in parallel, reserve the control port and interlock port, through the simple wiring can be connected in parallel. | ||||||||
Environment | Working environment | Ambient temperature-10°C-+40°C, relative humidity 0-95%, 100% fully loaded for 24 hours(when the ambient temperature exceeds the above temperature range, the machine can work normally, but the power must be reduced. | |||||||
IP class | IP32 | ||||||||
Cooling | Forced fan | ||||||||
Altitude | <1000M,can 100% full load working, >1000M, rated capacity need to be reduced accordingly | ||||||||
Others | Compressive strength | At 2500VAC for 1 minute, No breakdown fire,(leakage current <10mA) | |||||||
Cold insulation resistance | Measurement with 1000V ohms meter,>100MΩ | ||||||||
Noise | <55db | ||||||||
Dimension(LxWxH mm) | 4100x1500x2300 | 7100x1500x2300 | 8800x1500x2300 | ||||||
Weight(T) | 1.5T | 2T | 3T | 5.5T | 6T | 7.5T | 12T | 16T | |
Color | Color No.7032 |