Greencisco Industrial Co., Ltd.

-53.5Vdc Telecommunication Power

DC power system with -53.5VDC output for communication devices,CCTV, traffic lights,ect.

Characteristics

Application
Ethernet,Servers,Exchangers,Local area network (LAN) and metropolitan area network,Indoor wireless 
network,Telecommunications equipment,CCTV,Traffic lights,ect.
Introduction
It is a power supply of high capacity with two-way AC/DC outputs. The power supply adopts the latest circuit design, which has compact structure and reliable performance. The equipment has high accuracy and high output efficiency. With wide input voltage range, input overvoltage protection,output short-circuit protection, overcurrent protection and overtemperature protection. The cooling uses the natural heat dissipation of the system. 
The entire power supply is strictly designed in accordance with safety regulations and meets the requirements of information technology safety standards. With the following characteristics: Class D lightning protection capability, outdoor with high dust proof and waterproof design, protection level IP65, using contact heat dissipation on the bottom,with metal shell, the power supply housing and cable connector needs to be equipped with anti-off screws, support installation on the pole and wall. Which can be widely applied to the Base Station of GSM/CDMA, Exchange Bureau of medium-low capacity, Satellite Communication, Data Communication,mobile communication,Access network,microwave communication,electric power system,CCTV, traffic lights. ect.

Standards

Q/ZX 23.011.1-2004 Electromagnetic Compatibility Test Requirements for Communications Equipment-General Provisions

YD/T 731-2002 high frequency switching rectifier

ETSI 300 019 Environmental Engineering (EE);Environmental conditions and environmental tests for telecommunications equipment

ETSI EN 301 489-1 Electromagnetic compatibility and Radio spectrum Matters (ERM); Electromagnetic Compatibility (EMC) standard for radio equipment and services; Part 1: Common technical requirements

ETSI EN 301 489-8 Electromagnetic Compatibility and Radio spectrum Matters(ERM);Electromagnetic Compatibility(EMC) Standard for Radio Equipment and services;Part 8: Specific conditions for GSM Base stations

BS EN 55022 Information Technology Equipment-Wireless Interference Characteristics-Restriction and Measurement Method CEI IEC 60950-1999         Safety of information technology equipment

UL 60950  Safety of Information Technology Equipment

IEC61000-4 Electromagnetic compatibility (EMC); part 4: testing and measurement techniques

IEC 60529 AMD 1-1999 Degrees of protection provided by enclosures(IP code)

Specification

SP53.5M-B Telecommunication Power

Environment

Specification

Min

Standard

Max

Unit

Remark

Working temperature

-25


50

°C

-30°C,power supply can start work

Storage temperature

-30


85

°C


Humidity

5


95

%


Air pressure

70


106

KPa


Altitude



4000

m


Cooling





nature

Input

Specification

Min

Standard

Max

Unit

Remark

Input range

150

220

280

Vac


212


396

Vdc


Frequency

45

50

65

Hz


Power factor

0.95




Rated input, rated output(load current plus battery current 15A)

Output

Specification

Min

Standard

Max

Unit

Remark

Voltage range

-52

-53.5

-58

Vdc

Rated input, full load at test

Current



15

A


Voltage stabilizer accuracy



±2

%


Load adjustment rate



±1

%


Source adjustment rate



±1

%


Ripple+noise



200

mV


Efficiency

90



%

220Vac±20%/310Vdc±20% input,100% rated output

Output capacity


802


W


Temperature coefficient



±0.02%

/℃


Dynamic response overshoot



±5

%

25%~50%~25% or 50%~75%~50% load changes

Dynamic response recovery time



200

us

0.1A/ us

Overshoot value on and off



±5

%


Soft Start Time



8

S

Rated input voltage switch to output voltage established to set value