36V400Hz Frequency Converter for Aviation
The 36V/400Hz frequency converter power supply is designed and manufactured for Aviation and military electronic and electrical equipments.
Introduction
The 36V/400Hz frequency converter power supply is designed and manufactured for Aviation and military electronic and electrical equipment, which adopts high frequency switching technology. Can Be used in aircraft and airborne equipment, radar, navigation and other military electronic equipments, as well as other equipments which need 36V/400Hz power supply. The voltage and frequency of the converter can be adjustable at the range of 20%,suitable for three-phase unbalanced load, designated phase can also be used as a single-phase power supply.
Features
Meet the military standard of GJB572-88 and MIL-STD-704 technical requirements of aviation power specifications.
Intelligent control, using multi-CPU control, easy to monitor and experiment.
The operation is simple and convenient, and the operation parameters, operation records and fault information of the power supply can be checked through the display interface.
Adopted Siemens IGBT and Mitsubishi IGBT to drive, stable and excellent quality.
High stability, low drift, to meet the needs of high speed and very low distortion and ripple at the same time.
Adopt pulse width modulation (SPWM) technology to make smaller volume, light weight, low noise.
Excellent load protection function: with output over-voltage, under-voltage, phase fault, short-circuit output protection,ect.
Can be designed according to customer requirements, to ensure the safety of aircraft, equipment and operators.
Excellent self-protection function: Adopt intelligent IGBT IPM output, with automatic over-current, over-voltage protection and independent temperature detection protection circuit. In particular, phase-missing protection of three-phase power input.
Excellent overload protection: continuous operation at 120% overload, shutdown at 150% for 600 seconds, shutdown at 200% for 15 seconds. With isolation transformer: fully isolated output, long lifespane.
Fast output response: for 100% loading or unloading, the output voltage stabilizing rate is stable at 0.5% (linear load) within 2ms of the response time.
With good conduct and anti-radiation interference function.
Specification
Model | FC36400-01 | FC36400-02 | FC36400-03 | FC36400-05 | FC36400-06 | |
Capacity(KVA) | 1KVA | 2KVA | 3KVA | 5KVA | 6KVA | |
AC Input voltage | 220V±22V /380V ±40V | |||||
Phase | Single phase or three phases+3wires | |||||
Input Frequency | (50 / 60)Hz ±5Hz | |||||
AC Output voltage | 36/21VAC (28VAC-43VAC) | |||||
Output Frequency | 400Hz ±0.4Hz (320Hz-480Hz adjustable) | |||||
Transient | The maximum overshoot is ≤10% and the transient recovery time is ≤20ms | |||||
THD | ≤2% | |||||
Crest Coefficient | ≤1.41±0.10 | |||||
Single harmonic content | ≤1.5% | |||||
Voltage modulation amplitude | ≤2.5V | |||||
Display | Frequency | 0.1Hz, maximum difference:±0.1% | ||||
Voltage | 0.1V,maximum difference:±1V | |||||
Current | 0.1A,maximum difference:±2.5% | |||||
Capacity | 0.01KW,maximum difference:±5% | |||||
Efficiency | ≥85% | |||||
Three-phase voltage unbalance | Maximum difference≤1.5V | |||||
Phase shift | 120°±2° | |||||
Preset function | Standby state can be preset output voltage, output frequency, | |||||
Storage function | Output parameters will be automatic memory, when re-turn on the power, | |||||
Alarm function | The alarm signal is sent out after the protective device is operated | |||||
Protection | Input phase missing, output short circuit, output overvoltage, | |||||
Overload | 125% for 600 seconds,150% for 60seconds,200% for 15seconds, | |||||
Noise | ≤70dB | |||||
Display | LED display | |||||
Shell protection level | IP21; 0℃~+40℃ | |||||
Optional | Air Plug 2. Aerial Cable (10m, 15m, 20m) |